Collection Systems
Any references to the 15A NCAC 2H .0200 rules will be overridden by the new 2T Rules. Rule Highlights:
- Sewer extensions are mainly covered under 2T .0300.
- System-wide Collection System Permitting is covered under 2T .0400.
- The available power reliability option for pump stations can no longer be wet well storage for waters near Class C. Stations over 15,000 gallons per day require a permanent generator and those under require a portable generator receptacle. All stations now require telemetry/auto-dialer in addition to audible and visual alarms.
- For developer permitted projects, a copy of the Declarations must be submitted with the final engineering certification to demonstrate compliance with the terms of the Operational Agreement.
- More flow rates have been included in 2T .0114.
- Change of ownerships for private permitted projects (i.e. developer to homeowner association or public utility) must be submitted at the time of final certification.
- The separation distance between storm sewers and sanitary sewers has been increased to 24 inches unless structural bridging is provided.
- Separation distances between reclaimed water lines and wetlands and sanitary sewers has been added to 2T .0300.
Documents and Files
Sewer Line Permitting
For information regarding sewer line extention permits please visit the Construction Grants & Loans Website.